PYR-FA-CHA-XL

FIRE ALARM CONTROL PANEL

The PYR-FA-CHA-XL is a microprocessor based fire alarm control panel with 1 / 2 / 4 loops built-in supporting two-wire advanced communication. The panel communicates with the devices in real-time the detection data, the device status and control commands as well as monitors all internal components.

Specification

GENERAL

Technology

Microprocessor Based

Loops

1 / 2 / 4 Loop

Loop Capacity

255 devices

Expansion Loops

2 Loop Panels can be expanded to 4 Loops

Display

4.3” Color LCD Display

(480 x 272 Resolution)

Keypad

Numeric Easy-use Keypad

LED Indicators

Fire, Power, Fault, Power Fault, System Fault, Sounder Fault, Test, Delay, Evacuate, Sounder Disabled and 32 Zone Separate Indicators

Relays

1 for Fire Event

1 for Fault Event

Wiring

2 Wire (Polarity Insensitive)

Access Level

3

Log History

1,000 Event for Fire Event

1,000 Event for Fault Event

1,000 Event for Supervisory Event

Tests

Point Test, Zone Test and Module Test

Printer

Optional Integral Printer

 

MECHANICAL

Material

Cold Rolled Steel

Dimensions

560 mm x 430 mm x 170 mm

(Height x Width x Depth)

Weight

14 Kg (Without batteries)

 

PERFORMANCE

Panel Connection

CAN Bus (Can connect up to 20 panels for 1 and 2 Loop Panels and up to 10 panels for 4 loop panels)

Remote annunciator connection

RS485 (Can connect up to 30 RAPs)

Conventional DC Line Output

1 x 24 VDC Line, 500 mA

Class

Support A and B

Power Supply

Monitored with automatic change-over and battery charger

Battery Type

Value Regulated Lead Acid (VRLA)

Maximum Battery Capacity

12 VDC 17 Ah

ENVIRONMENTAL

Application

Indoor Installation Only

Operating Temperature

-5 °C to +45 °C

Storage Temperature

-10 °C to +55 °C

Humidity

0 to 95% (Relative Humidity)

 

ELECTRICAL

Mains Voltage

110 to 220 VAC ±15%

Operating Voltage

20 to 28 VDC

Standby Current

< 0.4 Ampere

Alarm Current

1 Ampere

 

REGULATORY

Certification

LPCB according to EN54-2 and EN54-4

Key Features

  • Modern Design and Feel
  • Easily Programmed
  • Each Loop supports 255 devices
  • Loop supports both Class A and B
  • 3” Color LCD Display
  • 1,000 Event Log for each event type
  • Automatic battery changeover and charge power supply
  • Can connect up to 20 panels for 1 and 2 loop panels and up to 10 panels for 4 loop panels
  • Can connect up to 30 remote annunciator panels
  • Can be divided to 32 zones with indicators
  • Independent 24VDC circuit
  • Multi-type tests
  • 3 Access Levels
  • 3 Year Warranty